Mitsubishi Electric Q01UCPU User Manual page 474

Hide thumbs Also See for Q01UCPU:
Table of Contents

Advertisement

(e) Auto refresh with an intelligent function module
This is the time required for refreshing data between the buffer memory of an intelligent function module and
devices in the CPU module.
 Calculation method
Calculate using the following formulas. Use the values in the following tables for KN1 and KN2.
(Refresh time) = KN1 + KN2 × (number of refresh points)
CPU module
Q00UJCPU
Q00UCPU, Q01UCPU
Q02UCPU
Q03UD(E)CPU
Q03UDVCPU, Q04UD(E)HCPU, Q04UDVCPU,
Q06UD(E)HCPU, Q06UDVCPU, Q10UD(E)HCPU,
Q13UD(E)HCPU, Q13UDVCPU, Q20UD(E)HCPU,
Q26UD(E)HCPU, Q26UDVCPU, Q50UDEHCPU,
Q100UDEHCPU
When the number of auto refresh points for the analog-digital converter module (Q64AD) is 4 points
Ex.
(when the module is mounted on the Q26UDHCPU main base unit)
(5) Function execution time in END processing
This is the time required for updating calendar or clearing error in END processing.
(a) Calendar update
The following processing time is required to change or read the clock data when the clock data set request
(SM210 changes from off to on) or the clock data read request (SM213 turns on) is issued.
Q00UJCPU, Q00UCPU, Q01UCPU
Q02UCPU
Q03UD(E)CPU, Q04UD(E)HCPU, Q06UD(E)HCPU, Q10UD(E)HCPU,
Q13UD(E)HCPU, Q20UD(E)HCPU, Q26UD(E)HCPU, Q50UDEHCPU,
Q100UDEHCPU
Q03UDVCPU, Q04UDVCPU, Q06UDVCPU, Q13UDVCPU,
Q26UDVCPU
472
0.024 (ms) = 0.004 + 0.005
CPU module
When an intelligent function
module is mounted on the
main base unit
KN1
KN2
96.3µs
6.7µs
96.3µs
6.7µs
23µs
6.0µs
6.0µs
5.0µs
4.0µs
5.0µs
4
×
Processing time in END processing
When the clock data set
request is issued
0.028ms
0.027ms
0.011ms
0.011ms
When an intelligent function
module is mounted on the
extension base unit
KN1
KN2
79.7µs
8.9µs
79.7µs
8.1µs
45µs
7.0µs
7.0µs
6.0µs
5.0µs
6.0µs
When the clock data
read request is issued
0.017ms
0.013ms
0.004ms
0.007ms