When the timer setting value is 2 (2 × 100ms), the scan time is 110ms, and the timer limit setting is 100ms
Ex.
If the coil of the timer (T0) is turned on at the next scan after the values satisfy "Count at execution of the
END instruction  Timer setting value", the coil and the contact are simultaneously turned on because the
values satisfy "Timer current value = Timer setting value" at the start of the timer.
Timer setting value
(2 100ms)
END
Program
100ms
1
counting
Count at
execution
1
of the END
instruction
Current
0
value of T0
OFF
X0
OFF
Coil of T0
Contact
OFF
of T0
110ms
(f) When the set value is changed after time-out
Even if the set value is changed to a larger value after time-out of the timer, the timer remains timed-out and
does not start the operation.
Scan time
Timer Limit Setting
(110ms)
END
END
1
2
1
2
0
0
ON
110ms
Timer setting value
(100ms)
X0
T0
END
1
1
2
ON
ON
110ms
CHAPTER 4 DEVICES
K2
If the coil is turned on for
this period, the contact
is simultaneously turned
on because the count at
execution of the END
instruction becomes
equal to or larger than
the timer setting value.
363
4