Toshiba Tosvert VF-S15 Instruction Manual page 154

Industrial inverter (for 3-phase induction motors)
Hide thumbs Also See for Tosvert VF-S15:
Table of Contents

Advertisement

6.10.5 Setting of frequency with the pulse train input
146 : Logic input / pulse train input selection (S2)
378 : Number of pulse train input
679 : Pulse train input filter
 Function
These parameters are used to set output frequency by means of pulse train input signal of S2
terminal.
[Parameter setting]
Title
Logic input / pulse train input selection
f146
(S2)
f378 Number of pulse train input
f679 Pulse train input filter
This function is valid when the parameter fmod =11 (Pulse train input) and f146 =1 (Pulse train
input) are set.
Number of pulses per 1Hz of output frequency is set by parameter f378.
Example of setting
f378 = 25 (pps) :
f378 = 50 (pps) :
Note 1) Minimum number of pulses to inputting S2 terminal is 10 pps, and Maximum is 2 kpps.
Duty is 50±10%.
Note 2) The maximum frequency output by this function is 200Hz.
Function
0: Logic input
1: Pulse train input
10-500 (pps)
2-1000 (ms)
Input signal = 25 (pps)
Input signal = 100 (pps)
Input signal = 2k (pps)
Input signal = 50 (pps)
Input signal = 100 (pps)
Input signal = 2k (pps)
F-43
Adjustment range
 Output frequency = 1.0 (Hz)
 Output frequency = 4.0 (Hz)
 Output frequency = 80.0 (Hz)
 Output frequency = 1.0 (Hz)
 Output frequency = 2.0 (Hz)
 Output frequency = 40.0 (Hz)
E6581926
Default setting
0
25
2
6