Toshiba Tosvert VF-S15 Instruction Manual page 216

Industrial inverter (for 3-phase induction motors)
Hide thumbs Also See for Tosvert VF-S15:
Table of Contents

Advertisement

6.29.7 Control mode for small current
f609 : Small current detection hysteresis
f610 : Small current trip/alarm selection
f611 : Small current detection current
f612 : Small current detection time
 Function
f610=0: No tripping. (Failure signal FL not activated)
f610=1: The inverter will trip if a current below the current set with f611 flows for the period of time
[Parameter setting]
6
Title
f609
f610
f611
f612
<Example of operation>
Output terminal function: 26 (UC) Low current detection
f610 = 0 (Alarm only)
Output current (%)
+
*
When setting f610 to 1 (Trip), trip after low current is detected for the period of time set with f612.
After tripping, the low current signal remains ON.
If the output current falls below the value set at f611 and doesn't return above f611+f609
for a time that exceeds the value set at f612, tripping or output alarm will be activated.
uc is displayed in the event of a trip.
A small current alarm can be put out from the output terminal.
specified with f612. (Failure signal FL activated)
Function
Small current detection hysteresis
Small current trip/alarm selection
Small current detection current
Small current detection time
Low current
signal output

Adjustment range
1-20 (%)
0: Alarm only
1: Tripping
0-150 (%) / (A)
0-255 (s)
OFF
 or less

Time [sec]
F-104
E6581926
Default setting
10
0
0
0
ON
OFF