6.32 Analog input terminal function selection
f214 : VIB input point 1 rate
f215 : VIB input point 2 rate
f663 : Analog input terminal function selection (VIB)
Function
Parameter is normally set from operation panel. However some parameters can be continuously set from
external analog input by using this function. VIB terminal is used.
[Parameter setting]
Title
f214 VIB input point 1 rate
f215 VIB input point 2 rate
Analog input terminal function
f663
selection (VIB)
Analog input terminal function assigns VIB terminal. The range of analog input voltage is 0% to +100%.
From -100% to 0% cannot be used.
The parameter that is selected by f663 can be adjusted range as following table.
Setting of f663
0: Frequency
command
1: Acceleration/
deceleration time
2: Upper limit
frequency
5: Torque boost
value
6: Stall prevention
level
7: Motor electronic-
thermal protection
level
11: Base frequency
voltage
Note: Adjustments are made by the inverter itself, so no changes are made to parameter settings
Function
-250-+250 (%)
-250-+250 (%)
0: Frequency command
1: Acceleration/deceleration time
2: Upper limit frequency
3, 4: -
5: Torque boost value
6: Stall prevention level
7: Motor electronic-thermal protection level
8 to 10: -
11: Base frequency voltage
12 to 23: -
Object parameter
-
-
acc , dec , f500 ,
Parameter setting value x
f501 , f510 , f511
f214
Parameter setting value x
ul
f214
Parameter setting value x
vb , f172
f214
Parameter setting value x
f185 , f601
f214
Parameter setting value x
thr , f173
f214
Parameter setting value x
vlv , f171
f214
F-117
Adjustment range
VIB : 0% input
-
Parameter setting value x
f215
Parameter setting value x
f215
Parameter setting value x
f215
Parameter setting value x
f215
Parameter setting value x
f215
Parameter setting value x
f215
E6581926
Default setting
0
100
6
0
VIB : 100% input