Checking The Region Settings Selection - Toshiba Tosvert VF-S15 Instruction Manual

Industrial inverter (for 3-phase induction motors)
Hide thumbs Also See for Tosvert VF-S15:
Table of Contents

Advertisement

4.4

Checking the region settings selection

set : Checking the region setting
If incorrect setting, the drive will have some damage or unexpected movement. Be sure to set
the setup menu correctly.
Mandatory
action
 Function
Set up menu performs automatic settings including base frequency of the motor according to the region
where the inverter is used. Also, the region selected on the setup menu can be checked.
[Parameter setting]
Title
Checking the region setting
set
* Default setting value is "jp".
 Content of region settings
The number displayed when parameter set is read indicates which of the following regions was selected on
the setup menu.
Note 1: 1 to 4 set to parameter set are read-only. Be aware that they cannot be written.
Set up menu starts by writing set = 0.
Related parameters including base frequency and base frequency voltage are automatically set.
Parameter settings can be changed individually even after selected at set up menu.
Note 2: Please note that all parameters return to status of default setting
Warning
Function
0: Start setup menu
1: Japan (read only)
2: North America (read only)
3: Asia (read only)
4: Europe (read only)
D-13
Adjustment range
and the trip history data is
E6581926
4
Default setting
1 *
cleared.