6.33 Adjustment parameters
6.33.1 Inputting integral input power pulse
: Integral input power pulse output unit
: Integral input power pulse output width
Function
[Parameter setting]
Title
Integral input power pulse output unit
6
Integral input power pulse output width
Setting example) When integral input power pulse is output from output terminal
Title
Output terminal selection 2A
There is no reverse signal.
6.33.2 Pulse train output for meters
f669 : Logic output/pulse train output selection (OUT)
f676 : Pulse train output function selection (OUT)
f677 : Maximum numbers of pulse train output
f678 : Pulse train output filter
Function
Ex.: When operations frequencies (0 to 60Hz) are put out by means of 0 to 600 pulses
Pulse signal can be output each time integral input power reaches integral power unit that is set by
f667 .
Pulse output width is set by f668 .
Function
Function
Pulse trains can be sent out through the OUT output terminals.
Set a pulse output mode and the number of pulses.
fh =60.0, f669 =1, f676 =0, f677 =0.60
Adjustment range
0: 0.1kWh
1: 1kWh
2: 10kWh
3: 100kWh
0.1-1.0 (s)
Adjustment range
0 - 255
F-118
E6581926
Default setting
1
0.1
Setting
180: IPU (Integral input
power pulse output signal)