Speed Instruction (Analog Signal) Settings From External Devices - Toshiba Tosvert VF-S15 Instruction Manual

Industrial inverter (for 3-phase induction motors)
Hide thumbs Also See for Tosvert VF-S15:
Table of Contents

Advertisement

7.3
Speed instruction (analog signal) settings from
external devices
Function of analog input terminals can be
selected from four functions (external
potentiometer, 0 to 10Vdc, 4 (0) to 20mAdc,
-10 to +10Vdc).
The selective function of analog input
terminals gives system design flexibility.
Default settings of slide switch SW1and SW2
are as follows;
SW1: SINK side, SW2: VIB side and S3 side.
Refer to page B-11 to 13 for details.
7
 Analog input terminal function settings
Terminal
symbol
VIA
VIB
VIC
VIA to VIC
*1: These are parameters set by setup menu. Default setting value is "jp". Refer to section 11.5.
Note1) When stable operation cannot be attained because of frequency setting circuit noise, increase the value of
f.
Note 2) Refer to section 5.8 when switching between two types of analog signals.
Title
Function

VIA input point 1 setting

VIA input point 1 frequency

VIA input point 2 setting

VIA input point 2 frequency
VIB input point 1 setting

VIB input point 1 frequency

VIB input point 2 setting

VIB input point 2 frequency

VIC input point 1 setting

VIC input point 1 frequency

VIC input point 2 setting

VIC input point 2 frequency

Analog input filter

[Control terminal block]
SW2
VIB
S4
S3
PTC
PP
VIA
VIB
CC
VIC
S3
NO
OUT
CC
P24
F
Adjustment range
0 - 100%
0.0 - 500.0Hz
0 - 100%
0.0 - 500.0Hz
-100 - +100%
0.0 - 500.0Hz
-100 - +100%
0.0 - 500.0Hz
0 - 100%
0.0 - 500.0Hz
0 - 100%
0.0 - 500.0Hz
2 - 1000 ms Note 1)
G-12
E6581926
SW1
SOURCE
SINK
PLC
FM
FLA
FLB
FLC
RY
STO
R
CC
+SU
S1
S2
RES
Default setting
0
0.0
100
60.0 *1
0
0.0
100
60.0 *1
20
0.0
100
60.0 *1
64
RC