Acceleration/Deceleration Time 2 And 3 - Toshiba Tosvert VF-S15 Instruction Manual

Industrial inverter (for 3-phase induction motors)
Hide thumbs Also See for Tosvert VF-S15:
Table of Contents

Advertisement

6.27 Acceleration/deceleration time 2 and 3

6.27.1 Selecting acceleration/deceleration patterns
f502 : Acceleration/deceleration 1 pattern
f506 : S-pattern lower-limit adjustment amount
f507 : S-pattern upper-limit adjustment amount
 Function
These parameters allow you to select an acceleration/deceleration pattern that suits the intended use.
Title
f502
f506
f507
6
1)
2)
Function
Acceleration/ deceleration 1 pattern
S-pattern lower-limit adjustment
amount
S-pattern upper-limit adjustment
amount
Linear acceleration/deceleration
A general acceleration/
deceleration pattern.
This pattern can usually be
used.
S-pattern 1 acceleration/deceleration
Select this pattern to accelerate/decelerate the motor rapidly to a high-speed region with an output
frequency of 60Hz or more or to minimize the shocks applied during acceleration/deceleration. This
pattern is suitable for pneumatic transport machines.
Output frequency [Hz]
Maximum frequency

Set frequency
0

Actual acceleration time
×
%



Adjustment range
0: Linear, 1: S-pattern 1, 2: S-pattern 2
0-50 (%)
0-50 (%)
Output frequency
[Hz]
Maximum frequency

0

Output frequency [Hz]
Maximum frequency

Set frequency
0
Time [s]
×

%

×
F-94
E6581926
Default setting
0
10
10
Time [s]


Time [s]
Actual deceleration time
×

%


%

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents