Building Automation
®
Maximum manual setpoint reduction
Options:
- 0 K
- 1 K
- 2 K
- 3 K
- 4 K
- 5 K
- 6 K
- 7 K
- 8 K
- 9 K
- 10 K
If you wish to prevent an excessive temperature reduction by the manual setpoint setting, the lower range of the
manual setpoint preset can be limited with the parameter "Maximum manual setpoint reduction".
Example: with a comfort cooling temperature of 26 °C and a manual setpoint adjustment of +/- 3 K, users can select
any temperature from 23 °C to 29 °C. If the comfort temperature can be reduced to a maximum of 25 °C, enter "1
K" under the parameter "Max. reduction of setpoint".
Object reset of manual setpoint adjustment active
Options:
- Yes
- No
This parameter releases a 1-bit communication object that upon receipt of an ON telegram can be used manually
reset the setpoint adjustment.
This is required, for instance, if a central function is triggered that is intended to reset all the room thermostats to their
default settings. All manual setpoint adjustments are rest for both "dependent" setpoints and "individual" setpoints.
When receiving base setpoint
Options:
- Retain manual setpoint adjustment
- Reset manual setpoint adjustment
If a new base setpoint is received by the ambient temperature controller via KNX telegram after manually adjusting
the setpoint, the ambient temperature controller can also reset the manually adjusted setpoint. The behaviour of
the ambient temperature controller when receiving a base setpoint value can be configured via this parameter.
The manually configured setpoint is either reset or remains unchanged. This refers to all setpoints for "dependent"
setpoints and the base setpoint that was received for "individual" setpoints, e.g. "heating setpoint comfort mode".