MYLOS
Building Automation
®
6
Party mode
This 1-bit communication object can be used to deactivate party mode
when an ON telegram is received. This
communication object can be used, e.g., by time switches to send information.
This data item forms the 1-bit object of KNX for switching operating modes (party mode).
0: party mode Off
7
Holiday mode
This 1-bit communication object can be used to deactivate holiday mode
when an ON telegram is received. This
communication object can be used, e.g., by time switches to send information.
This data item forms the 1-bit object of KNX for switching operating modes (holiday mode).
0: holiday mode Off
8
Operating mode switching
This data item forms the 1-bit object of KNX (DPT_HVAC_MODE) for switching operating
modes. All operating modes of the above 1-bit objects can be set with the 1-byte object.
The data item can be received and sent. The selection of whether switching is via three 1-bit
objects or two 1-byte objects (OMN / OMO) is defined by application parameters (see above).
This 1-byte communication object can be used to switch between comfort, standby, night
and frost/heat protection modes. The object evaluates received telegrams as „normal".
This means, for example, if a comfort telegram is received, the room thermostat switches
to comfort mode. If a night telegram is received, the room thermostat switches to night mode.
This object is controlled, for example, by time switches.
The following provisions apply for the object:
0: Auto
1: Comfort
2: Standby
3: Night
4: Frost/Heat Protection
5: Party
6: Holiday
7 – 255: not allowed
26
Exter. via object Switching
This data item forms the 1-bit KNX object. It can be received and sent. If the RTR switches
the operating mode, the object is sent if the corresponding parameter has been set to
„automatic and send". In the event of external switching the operating mode is switched by
a different bus device (such as a fan coil 2-line system). After the switching a separate output
object or the same output object can be used (depending on the number of output channels
with „heating and cooling").
0: cooling
1: heating
56 Commissioning | MYLOS
Building Automation
®
Commissioning
Operating mode
1 bit EIS1 DPT 1.001
Operating mode
1 bit EIS1 DPT 1.001
Operating mode
1 byte EIS1 DPT
20.102
Operating mode
1 bit EIS1 DPT 1.001
C,R,W
C,R,W
C,R,W
C,R,W,T