Fan Coil - ABB 2CSYK1201C Product Manual

Mylos knx
Table of Contents

Advertisement

MYLOS
Building Automation
Planning and use
®
7.3.4

Fan Coil

If fan coil is selected under "control types", the control values are output in the same way as described at continuous
controllers.
A fan coil also has the option of controlling fan stages using a 1-byte or three 1-bit communication objects with a
fan coil actuator.
Switching fan stages will heat or cool a room faster.
The fan stage that is to be enabled at which control value is defined on a separate tab, "fan coil heating" or "fan coil
cooling". Note that the threshold values must not overlap, i.e. the stage 1 threshold value must always be less that
the stage 2 threshold value, which in turn must be less than the stage 3 threshold value.
MYLOS
Building Automation | Planning and use 71
®

Advertisement

Table of Contents
loading

This manual is also suitable for:

2csyk1201s

Table of Contents