4.5. Examples of the use of communication commands
Here are some examples of the use of communication commands provided for the VF-S15 series of
inverters.
Inverter numbers and checksum used in ASCII mode are omitted from these examples.
Examples of communication
- To run the motor in forward direction with the frequency set to 60 Hz from the computer
<ASCII mode>
Computer Inverter
(PFA011770)
(PFA00C400)
<Binary mode>
Computer Inverter
2F 50 FA 01 17 70 01
2F 50 FA 00 C4 00 3D
- To monitor the output frequency (during 60 Hz operation)
<ASCII mode>
Computer Inverter
(RFD00)
<Binary mode>
Computer Inverter
2F 52 FD 00 7E
- To monitor the status of the inverter
<ASCII mode>
Computer Inverter
(RFD01)
<Binary mode>
Computer Inverter
2F 52 FD 01 7F
- To check the trip code (when the inverter is tripped because of err5)
<ASCII mode>
Computer Inverter
(RFC90)CR
<Binary mode>
Computer Inverter
2F 52 FC 90 0D
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Inverter Computer
(PFA011770)
CR
(PFA00C400)
CR
Inverter Computer
2F 50 FA 01 17 70 01
2F 50 FA 00 C4 00 3D
Inverter Computer
(RFD001770)
CR
Inverter Computer
2F 52 FD 00 17 70 05
Inverter Computer
(rFD010003)
CR
Inverter Computer
2F 72 FD 01 00 03 A2
...For details on trip codes, see "Trip code monitor" in "8.2. Monitoring
from the computer". (18H = 24d "err5" trip status)
Inverter Computer
(rFC900018)CR
Inverter Computer
2F 72 FC 90 00 18 45
...Set the operation frequency to 60 Hz.
CR
(60 / 0.01 Hz = 6000 = 1770H)
...Set to "forward run" with commands and frequency
CR
instruction from the computer enabled.
...Set the operation frequency to 60 Hz.
CR
(600.01Hz=6000=1770H)
...For details on statuses, see "8.2. Monitoring from
CR
the computer". (Stop status, FL output status, trip
status (r command))