Toshiba Tosvert VF-S15 Series Instruction Manual page 29

Rs485 communication function
Hide thumbs Also See for Tosvert VF-S15 Series:
Table of Contents

Advertisement

8) Read data 5 (2 bytes)
9) CRC16 (2 bytes)
 Inverter → Computer (Abnormal return) *The text size is 5 bytes fixed.
Inverter
Command Error Code
No.
83
1) Inverter No (1 byte)
2) Command (1 byte)
3) Error code (1 byte)
4) CRC16 (2 bytes)
 Example: Indirect block read of 5 words(During 60Hz operation)
< Parameter >
f802 (Inverter number) = 1
f829 (Selection of communication protocol) = 1: Modbus RTU
f875 (Block read data 1) =1: Ststus information 1
f876 (Block read data 2) = 2: Output frequency
f877 (Block read data 3) = 3: Output current
f878 (Block read data 4) = 4: Output voltage
f879 (Block read data 5) = 5: Alarm information
(Computer → inverter)
(Inverter → computer)
 Example: Indirect block read of 2 words(During 60Hz operation and f875=1, f876=2)
(Computer → inverter)
(Inverter → computer)
 Example: Indirect block read of 2 words(During 60Hz operation and f875=0, f876=2)
(Computer → inverter)
(Inverter → computer)
 Example: Data error ( Number of word is wrong )
(Computer → inverter)
(Inverter → computer)
 Example: Data error ( Communication number is wrong )
(Computer → inverter)
(Inverter → computer)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
: The data selected with f879 is read.
: ---
CRC16
low
high
: ---
: 83H fixed (Read command error) (Command + 80H)
: See "5.3. Error codes".
: ---
01 03 18 75 00 05 92 B3
01 03 0A E4 04 17 70 00 00 26 FF 00 80 58 00
01 03 18 75 00 02 D3 71
01 03 04 E4 04 17 70 83 16
01 03 18 75 00 02 D3 71
01 03 04 00 00 17 70 F4 27
01 03 18 75 00 06 D2 B2
01 83 03 01 31
01 03 18 76 00 02 23 71
01 83 03 01 31