Baud Rate (F800), Parity (F801); Inverter Number (F802) - Toshiba Tosvert VF-S15 Series Instruction Manual

Rs485 communication function
Hide thumbs Also See for Tosvert VF-S15 Series:
Table of Contents

Advertisement

7.1. Baud rate (f800), Parity (f801)

Communication baud rate and parity bit should be uniform inside the same network.
This parameter is validated by resetting the power supply.

7.2. Inverter number (f802)

This parameter sets individual numbers with the inverters.
Inverter numbers should not be duplicated inside the same network.
Receiving data will be canceled if inverter numbers specified in individual communication and set by
a parameter do not match.
This parameter is validated from the communication after change
Data range: 0 to 247 (Initial value: 0)
Parameters can be selected between 0 and 247. Note that the communication protocols limit
inverter numbers as follows:
● Toshiba inverter protocol ASCII mode: 0 to 99
● Toshiba inverter protocol Binary mode: 0 to 63
● Modbus RTU protocol: 0 to 247 (0: Broadcast communication)