Block Read Command:direct (03H) - Toshiba Tosvert VF-S15 Series Instruction Manual

Rs485 communication function
Hide thumbs Also See for Tosvert VF-S15 Series:
Table of Contents

Advertisement

5.1.3.Block Read command:Direct (03H)
The data of consecutive communication number from the specified communication number is read.
Eight data or less is read. When a consecutive communication number doesn't exist, the data of
8000H is sent back.
 Computer → Inverter *The text size is 8 bytes fixed.
Inverter
Com-
No.
mand
03
1) Inverter No. (1 byte)
2) Command (1 byte)
3) Communication No. (2 bytes)
4) Number of data groups (2 bytes) : Set the number of data words from 0002H to 0008H.
5) CRC16 (2 bytes)
 Inverter → Computer *The text size is variable.
Inverter
Com-
mand
No.
03
1) Inverter No. (1 byte)
2) Command (1 byte)
3) Number of data (1 bytes)
4) Read data 1 (2 bytes)
5) Read data 2 (2 bytes)
6) Read data 3 (2 bytes)
7) Read data 4 (2 bytes)
8) Read data 5 (2 bytes)
9) Read data 6 (2 bytes)
10) Read data 7 (2 bytes)
11) Read data 8 (2 bytes)
12) CRC16 (2 bytes)
 Inverter → Computer (Abnormal return) *The text size is 5 bytes fixed.
Inverter
Command Error Code
No.
83
1) Inverter No (1 byte)
2) Command (1 byte)
3) Error code (1 byte)
4) CRC16 (2 bytes)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Communication
Number of Data
No.
Groups
high
low
high
00
: ---
: Set the read command (03H fixed).
: Set in the order of high to low numbers.
Note: If communication number doesn't exist, return the error to computer.
: ---
Number
Read data 1
of data
high
low
04-16
: ---
: Set the read command (03H fixed).
: A number of data bytes will be returned. The number of data groups for transmis-
sions to the inverter is from 04 to 16 (04H – 10H) bytes. Note that the number of
data returned by the inverters is variable.
: The data of specified communication number is read.
: The data of specified communication number + 1 is read.
: The data of specified communication number + 2 is read.
: The data of specified communication number + 3 is read.
: The data of specified communication number + 4 is read.
: The data of specified communication number + 5 is read.
: The data of specified communication number + 6 is read.
: The data of specified communication number + 7 is read.
: ---
CRC16
low
: ---
: 83H fixed (Read command error) (Command + 80H)
: See "5.3. Error codes".
: ---
CRC16
low
low
high
02-08
Read data 8
...
high
low
high
29
E6581913
CRC16
low
high