5.1.2. Block Read command:Indirect (03H)
Select the read data which is desired to be read in block communication to Block Communication
Read Data Parameters (f875 to f879). This parameter becomes effective when the system
is reset, such as when power is turned off. When the setting is completed, turn off and then on the
power.
No.
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
* "0000" will be returned as dummy data, if "0 (No selection)" is selected for the parameter and
"read" is specified.
 Computer → Inverter *The text size is 8 bytes fixed.
Inverter
Com-
No.
mand
03
1) Inverter No. (1 byte)
2) Command (1 byte)
3) Communication No. (2 bytes)
4) Number of data groups (2 bytes) : Set the number of data words from 0002H to 0005H.
5) CRC16 (2 bytes)
 Inverter → Computer *The text size is variable.
Inverter
Com-
mand
No.
03
1) Inverter No. (1 byte)
2) Command (1 byte)
3) Number of data (1 bytes)
4) Read data 1 (2 bytes)
5) Read data 2 (2 bytes)
6) Read data 3 (2 bytes)
7) Read data 4 (2 bytes)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Block read data
No selection
Status information 1 (FD01)
Output frequency (FD00)
Output current (FD03)
Output voltage (FD05)
Alarm information (FC91)
PID feedback value (FD22)
Input terminal monitor (FD06)
Output terminal monitor (FD07)
Terminal VIA monitor (FE35)
Terminal VIB monitor (FE36)
Terminal VIC monitor (FE37)
Input voltage (FD04)
Motor speed (FE90)
Torque (FD18)
Communication
Number of Data
No.
Groups
high
low
high
18
75
00
: ---
: Set the read command (03H fixed).
: Set in the order of high to low numbers (1875H fixed).
: ---
Number
Read data 1
of data
high
low
04-10
: ---
: Set the read command (03H fixed).
: The number of read data bytes will be returned. The number is from 04H to 0AH
bytes. Note that the number of byte is variable.
: The data selected with f875 is read.
: The data selected with f876 is read.
: The data selected with f877 is read.
: The data selected with f878 is read.
For data details, see:
-
"8.2. Monitoring from communication"
"9. Parameter data"
"8.2. Monitoring from communication"
"9. Parameter data"
"8.2. Monitoring from communication"
CRC16
low
low
high
02-05
Read data 5
...
high
low
low
27
E6581913
CRC16
high

Hide quick links:

Advertisement

Table of Contents
loading