Table 16. Location requirements (continued)
Criteria
Air quality
Technical specifications for this library can be referenced in the following tables.
Physical specifications
Table 17. Physical specifications
Characteristic
Height
|
Width
Depth
Weight
1
|
Includes front covering of rack rails, allowing for magazine opening clearance.
Electrical specifications
Table 18. Electrical specifications
Characteristic
Current
Voltage
Power
Equipment environmental specifications
Table 19. Equipment environmental specifications
ML3
Dry bulb
temperature
(deg C)
Allowable Recom-
15 to 32
Notes:
v Derate maximum dry-bulb temperature 1°C/300 in (34°F/984 ft.) above 900 m (2,953 ft.).
v Derate maximum recommended dry-bulb temperature 1°C/300 in (34°F/984 ft.) above 1,800 m (5,905 ft.).
24
Dell EMC ML3 Tape Library: User's Guide
Definition
v Place the library in an area with minimal sources of particulate contamination.
v Avoid areas near frequently used doors and walkways, stacks of supplies that
collect dust, printers, and smoke-filled rooms.
v Excessive dust and debris can damage tapes and tape drive.
Product alone
133 mm
1
480 mm
873 mm
Base module: 21 Kg
Expansion module: 13 Kg
Operating environment
Relative Humidity
(%RH, non-
condensing)
Allowable Recom-
mended
mended
16 to 25
20 to 80
20 to 50
Packaged
694 mm
667 mm
1194 mm
Base module: 30 Kg
Expansion module: 23 Kg
Specification
5.0 - 3.5 A
100 - 240 V 50/60 Hz
350 W
Max wet
Max
bulb
elevation
tempera-
(meters)
ture
(deg C)
26
3050
Product power off
Dry bulb
Relative
Max wet
tempera-
Humidity
bulb
ture
(%RH,
tempera-
(deg C)
non-
ture
condens-
(deg C)
ing)
5 to 45
8 to 80
26