ACS800-07/U7
Frame
type
size
690 V units
-0070-7
R6
-0100-7
R6
-0120-7
R6
-0145-7
R6
-0175-7
R6
-0205-7
R6
-0260-7
R7
-0320-7
R8
-0400-7
R8
-0440-7
R8
-0490-7
R8
-0550-7
R8
-0610-7
R8
P
Maximum braking power of the drive with the specified resistor(s). The drive and the chopper will withstand this
br5
braking power for 5 seconds per minute.
P
The drive and the chopper will withstand this braking power for 10 seconds per minute.
br10
P
The drive and the chopper will withstand this braking power for 30 seconds per minute.
br30
P
The drive and the chopper will withstand this continuous braking power. The braking is considered continuous if the
brcon
braking time exceeds 30 s.
t
Note: Check that the braking energy transmitted to the specified resistor(s) in 400 seconds does not exceed E
R
Resistance value for the resistor assembly. Note: This is also the minimum allowed resistance for the brake
resistor.
E
Short energy pulse that the resistor assembly withstands every 400 seconds. This energy will heat the resistor
R
element from 40 °C (104 °F) to the maximum allowable temperature.
P
Continuous power (heat) dissipation of the resistor when placed correctly. Energy E
Rcont
*
ACS800-0x types only
**
ACS800-Ux types only
1)
240 kW possible if ambient temperature is below 33 °C (91 °F)
2)
160 kW possible if ambient temperature is below 33 °C (91 °F)
3)
630 kW possible if ambient temperature is below 33 °C (91 °F)
4)
450 kW possible if ambient temperature is below 33 °C (91 °F)
5)
160 kW possible if ambient temperature is below 33 °C (91 °F)
Braking power of the chopper and
the drive
5/60 s
10/60 s
30/60 s
P
P
P
br5
br10
br30
(kW)
(kW)
(kW)
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
5)
135
120
100
300
300
300
375
375
375
430
430
430
550
400
315
550
400
315
550
400
315
Brake resistor(s)
Type
P
brcont
(kW)
45
SAFUR90F575
55
SAFUR80F500
75
SAFUR80F500
160
SAFUR80F500
160
SAFUR80F500
160
SAFUR80F500
80
SAFUR80F500
260
SAFUR200F500
375
SAFUR200F500
385
SAFUR200F500
225
2xSAFUR125F500
225
2xSAFUR125F500
225
2xSAFUR125F500
R
E
P
R
Rcont
(ohm)
(kJ)
(kW)
8.00
1800
4.5
6.00
2400
6
6.00
2400
6
6.00
2400
6
6.00
2400
6
6.00
2400
6
6.00
2400
6
2.70
5400
13.5
2.70
5400
13.5
2.70
5400
13.5
2.00
7200
18
2.00
7200
18
2.00
7200
18
00096931-J
dissipates in 400 seconds.
R
Resistor braking