Control Cable Ducts - ABB ACS800-U7 Hardware Manual

Acs800 45 to 560 kw; 50 to 600 hp
Hide thumbs Also See for ACS800-U7:
Table of Contents

Advertisement

A diagram of the cable routing is shown below.
Input power cable
min 200 mm (8 in.)

Control cable ducts

Not allowed unless the 24 V cable is
insulated for 230 V (120 V) or insulated
with an insulation sleeving for 230 V
(120 V).
Drive
90 °
Control cables
230 V
(120 V)
24 V
Motor cable
min 300 mm (12 in.)
Power cable
Motor cable
min 500 mm (20 in.)
230 V
(120 V)
24 V
Lead 24 V and 230 V (120 V) control
cables in separate ducts inside the
cabinet.
Planning the electrical installation