Second Environment (Drive Of Category C3); Second Environment (Drive Of Category C4); Machinery Directive - ABB ACS800-U7 Hardware Manual

Acs800 45 to 560 kw; 50 to 600 hp
Hide thumbs Also See for ACS800-U7:
Table of Contents

Advertisement

Second environment (drive of category C3)

The drive complies with the standard with the following provisions:
1. The drive is equipped with EMC filter E200 [suitable for TN (earthed) systems] or E210 [suitable for
TN (earthed) and IT (unearthed) systems].
2. The motor and control cables are selected as specified in the Hardware Manual.
3. The drive is installed according to the instructions given in the Hardware Manual.
4. Maximum cable length is 100 metres.
WARNING! A drive of category C3 is not intended to be used on a low-voltage public network which
supplies domestic premises. Radio frequency interference is expected if the drive is used on such a
network.

Second environment (drive of category C4)

If the provisions under
the standard can be met as follows:
1. It is ensured that no excessive emission is propagated to neighbouring low-voltage networks. In
some cases, the natural suppression in transformers and cables is sufficient. If in doubt, the supply
transformer with static screening between the primary and secondary windings can be used.
Point of measurement
Low voltage
Equipment
2. An EMC plan for preventing disturbances is drawn up for the installation. A template is available
from the local ABB representative.
3. The motor and control cables are selected as specified in the Hardware Manual.
4. The drive is installed according to the instructions given in the Hardware Manual.
WARNING! A drive of category C4 is not intended to be used on a low-voltage public network which
supplies domestic premises. Radio frequency interference is expected if the drive is used on such a
network.

Machinery Directive

The drive is an electronic product which is covered by the European Low Voltage Directive. However,
the drive can be equipped with the Safe torque off function and other safety functions for machinery
which, as safety components, are in the scope of the Machinery Directive. These functions of the drive
comply with European harmonized standards such as EN 61800-5-2. The declaration of conformity for
each function is in the appropriate function-specific manual.
Second environment (drive of category C3)
Medium voltage network
Neighbouring network
Equipment
(victim)
cannot be met, the requirements of
Supply transformer
Static screen
Low voltage
Drive
Equipment
133