C O N F I G U R I N G T H E M OTO R P R OT E C T I O N F U N C T I O N S

Voltage and Power Protection Functions

This section describes the voltage based motor protection functions. The UMC100.3 together with the voltage module VI150/VI155
continuously measures the motor supply voltage (line to line), the motor current and the phase angle between the current and vol-
tage. The power and energy consumption is calculated out of these values and used for various protection and monitoring func-
tions. The different process values can be reported to the fieldbus and displayed on the LCD panel.
The following functions are described in this section:
• Overvoltage, Undervoltage
• Phase loss
• Voltage imbalance
• Total harmonic distortion
The following process data are available:
Process Value
Explanation
The power factor is defined as the ratio of the real power flowing to
the load to the apparent power and is a non dimensional number
between 0 and 1
(also expressed as a percentage).
Powerfactor (cosphi)
The cos phi only considers the fundamental frequency.
In this manual both terms are used and refer to the fundamental
frequency only!
U
, U
, U
Phase to phase (line to line) voltages (three-phase mode)
L1L2
L2L3
L3L1
U
Phase to neutral (single-phase mode)
LN
Active power is the capacity of the motor for performing work in a
Active power
particular time
Apparent power
The apparent power is the vector sum of real and reactive power.
Voltage Imbalance
An imbalance between the supply voltages in the network.
Total harmonic
Harmonic distortion of the mains.
distortion (THD)
Energy
Consumed energy.
In section 2 -> Connecting the VI15x Voltage Module you will find information on how to mount and connect the
voltage module.
All process values generated from the voltage module can be used in the Custom Application Editor. Consult the
editor's manual for more information.
The digital output of the voltage module DO0 can be freely used in the function block editor.
By default it is connected to the command telegram and can be controlled from a PLC.
Before using the voltage module set the following parameters:
• Nominal line to line voltage (three-phase mode)
• Nominal to neutral voltage (single-phase mode)
• Nominal power factor (cos phi)
• VI15x enabled.
If the module is enabled the UMC monitors the presence of the module and creates by default
a fault in the event that the module is missing (-> parameter 'Missing Module Reaction').
• Overload, Underload
• Power factor
• Voltage Dip reaction
Data range
0...1 (0 ... 100%)
0...115% of U
e
0...65535 [1 W, 10 W, 100 W, 1 kW]
The actual unit depends on the selected scaling factor.
0...65535 [1 VA, 10 VA, 100 VA, 1 kVA]
The actual unit depends on the selected scaling factor.
0 ... 100 %
0 ... 100 %
kWh
49