U M C 1 0 0 . 3 U N I V E R S A L M O T O R C O N T R O L L E R T E C H N I C A L D E S C R I P T I O N
24

Motor Wiring

The following diagram shows different methods of connecting a motor. For a reliable motor protection it is essential to set
the correct nominal current I
Note:
For inner-delta wiring the parameter Current Factor needs to be set to 1.73 (=√3). The √3 circuitry is normally used for larger
motors to reduce the current transformer size.
Single phase
Power line
Power line: 690 V
L1
L2
N
L
UMC
UMC
N
L
U1
1
W2
Example for motor:
Example for motor:
Motor rating plate
Motor rating plate
230 V
400 V / 690 V
4.9 A / 2.8 A
2.5 A
I
= 2.5 A
I
= 2.8 A / I
e
P
Parameter
Parameter
Set Current = 2.80
Set Current = 2.50
Current factor = 100
Current factor = 100
Terminal box
U1
W2
I
= Actual current / phase
P
I
= Set current
SC
It is optional to feed N through the UMC if ground fault detection is disabled.
Related Parameters:
• Nominal current Ie1
• Current factor
.
e
Star
Delta
Power line: 400 V
I
P
L1
L2
L3
L3
UMC
I
=
SC
I
P
V1
W1
U1
V1
W1
U2
V2
W2
U2
V2
Example for motor:
Motor rating plate
400 V / 690 V
4.9 A / 2.8 A
= 2.8 A
I
= 4.9 A / I
SC
P
SC
Parameter
Set current = 4.90
Current factor = 100
Terminal box
V1
W1
U1
V1
W2
U2
V2
U2
3 wiring
Power line: 400 V
I
I
P
P
L1
L2
L3
UMC
I
=
SC
I
P
U1
V1
W1
W2
U2
V2
Example for motor:
Motor rating plate
400 V / 690 V
4.9 A / 2.8 A
= 4.9 A
I
= 4.9 A / I
= Ip/√3=2.80
P
SC
Parameter
Set current = 4.9
Current factor = 173
Terminal box
W1
U1
V1
W1
W2
V2
U2
V2
I
=
SC
I
* 0.577
P