PA R A M E T E R S A N D D ATA S T R U C T U R E S O N A F I E L D B U S

VI150-FBP.0 / VI155-FBP.0 Parameters

Parameter
Parameter
Number
Name
4
VI15x Enabled
158
Nominal Line
Voltage
159
U Low Trip
Level
160
U Low Trip
Delay
161
U Low Warn
Level
162
U Low Warn
Delay
163
U High Trip
Level
164
U High Trip
Delay
165
U High Warn
Level
166
U High Warn
Delay
200
PwrFactor Trip
Level
201
PwrFactor Trip
Delay
202
PwrFactor
Warn Level
203
PwrFactor
Warn Delay
204
U Imb. Trip
Level
205
U Imb. Trip
Delay
206
U Imb. Warn
Level
207
U Imb. Warn
Delay
208
P Low Trip
Level
209
P Low Trip
Delay
210
P Low Warn
Level
211
P Low Warn
Delay
Description, Explanations
Specify if the module is connected to UMC
In three-phase mode:
Line to Line Voltage e.g. 190V, 400V or 690V
In single-phase mode:
Line to Neutral Voltage e.g. 110V, 240V, 400V
Value in % of U/Ue. Below this value a trip is generated.
Delay time until a low voltage trip is triggered.
Value in % of U/Ue. Below this value a warning is generated.
Delay time until a low voltage warning is triggered.
Value in % of U/Ue. Above this value a trip is generated.
Delay time until a high voltage trip is triggered.
Value in % of U/Ue. Above this value a warning is generated.
Delay time until a high voltage warning is triggered.
Power factor (cos phi). Below this value a trip is generated.
30 disables the function
Delay time until a low power factor trip is triggered.
Power factor (cos phi). Below this value a warning is
generated.
30 disables the function
Delay time until a low power factor warning is triggered
Voltage imbalance trip level
20 disables the function
Delay time until an imalance trip is triggered
Voltage imbalance warning level
20 disables the function
Delay time until an imalance warning is triggered
Below this value a trip is generated
20 disables the function
Delay time until an low power trip is triggered
Below this value a warning is generated.
20 disables the function
Delay time until an low power warning is triggered
Options
0: Off
1: On
U
: 90...690V in steps of 1V (up to
e
400V in single-phase mode)
Default: 400V
70 ... 100%
70 disables the function
0...25.5s in steps of 0.1s
Default: 3s
Unscaled: 0...255
Example: 20 means 2s
70 ... 100%
70 disables the function
0...25.5s in steps of 0.1s
Default: 3s
Unscaled: 0...255
Example: 20 means 2s
100 ... 116% of Ue in steps of 1%
116% disables the function
0...25.5s in steps of 0.1s
Default: 3s
Unscaled: 0...255
Example: 20 means 2s
100 ... 116% of Ue in steps of 1%
116% disables the function
0...25.5s in steps of 0.1s
Default: 3s
Unscaled: 0...255
Example: 20 means 2s
0.30 ... 1 in steps of 0.01
Unscaled: 30...100
Example: 75 means a PF of 0.75
0...25.5s in steps of 0.1s
Default: 3s
Unscaled: 0...255
Example: 20 means 2s
0.30 ... 1 in steps of 0.01
Unscaled: 30...100
Example: 75 means a PF of 0.75
0...25.5s in steps of 0.1s
Default: 3s
Unscaled: 0...255
Example: 20 means 2s
0.2 ... 20% in steps of 0.1%
Unscaled 2..200
0...25.5s in steps of 0.1s
Default: 1s
Unscaled: 0...255
Example: 20 means 2s
0.2 ... 20% in steps of 0.1%
Unscaled 2..200
0...25.5s in steps of 0.1s
Default: 1s
Unscaled: 0...255
Example: 20 means 2s
20 ... 100% in steps of 1%
0...255s in steps of 1s
Default: 5s
20 ... 100% in steps of 1%
0...255s in steps of 1s
Default: 5s
133
Adjustable via
All
All excluding GSD-PDQ22
All excluding GSD-PDQ22
All excluding GSD-PDQ22
All excluding GSD-PDQ22
All excluding GSD-PDQ22
All excluding GSD-PDQ22
All excluding GSD-PDQ22
All excluding GSD-PDQ22
All excluding GSD-PDQ22
All excluding GSD-PDQ22
All excluding GSD-PDQ22
All excluding GSD-PDQ22
All excluding GSD-PDQ22
All excluding GSD-PDQ22
All excluding GSD-PDQ22
All excluding GSD-PDQ22
All excluding GSD-PDQ22
All excluding GSD-PDQ22
All excluding GSD-PDQ22
All excluding GSD-PDQ22
All excluding GSD-PDQ22