PA R A M E T E R S A N D D ATA S T R U C T U R E S O N A F I E L D B U S

Protection Parameters

Parameter
Parameter
Number
Name
Protection Parameters
29
Setting I
e1
30
Setting I
e2
28
Trip class
31
Current factor
9
PTC, Thermistor
48
Cooling mode
49
Cooling time
50
Restart level
in %
146
Thermal load
warning level
Locked Rotor
40
Locked rotor
trip level
41
Locked rotor
trip delay
Description, Explanations
Nominal current of motor for speed 1.
Nominal current of motor for speed 2.
Class according to EN/IEC
60947-4-1
Current factor when using an external CT or when the motor wires
are fed through the UMC CTs more than once.
Setting for the built-in PTC (Thermistor) protection. The reaction
to hardware cannot be set separately.
After a thermal overload trip which was triggered through the
thermal motor model the cooling duration can be defined as fixed
time or as a percentage of the thermal load level (0%=cold, 100%
= trip)
The time a restart is inhibited following a thermal overload trip
triggered by the thermal motor model
Below this threshold a motor restart is accepted.
If the thermal model reaches the warning level a warning is
generated.
Current in percentage that should trigger a locked rotor fault
during motor start-up. A value of 800% (160) switches off the
function.
The time the motor current must exceed the adjusted threshold
before a fault is triggered.
Options
0.24...3200A in steps of 0.01A
Default: 0.50A
Unscaled: 24...320000
Example: A value of 24 means
240mA
See above
Class 5 (0),
Class 10 (1),
Class 20 (2),
Class 30 (3),
Class 40 (4)
2,3,4,5, 100 ... 64000
Examples:
3: motor wires are fed through 3
times
100: internal CT, no multiple
feed-throughs
12500 means a factor of
125:1
Disabled (0),
Trip(1),
Warning(2)
Time (0),
Restart Level (1)
30 ... 64000s
Default value: 120s
10...100%
Default value: 30%
20 ... 100
100% ... 800% in steps of 5%
800% disables the function
Unscaled: 20 ... 160
Example: 100 means 500%
0, 0.1, 0.2, 0.3, 0.4, 0.5 ... 25.5s in
steps of 0.1s
Unscaled: 0...255
Example: 5 means 500ms
127
Adjustable via
All
All
All
All
All
All
All
All excluding
GSD-PDQ22
All excluding
GSD-PDQ22
All
All