Resetting Parameters To Factory Defaults; Resetting The Password; Reading, Setting And Resetting Maintenance Counters; I/O-Module Status Codes - ABB UMC100.3 Manual

Univeral motor controller
Hide thumbs Also See for UMC100.3:
Table of Contents

Advertisement

U M C 1 0 0 . 3 U N I V E R S A L M O T O R C O N T R O L L E R T E C H N I C A L D E S C R I P T I O N
118

Resetting parameters to factory defaults

It is possible to reset all parameters to the factory default settings. The fieldbus address is not affected from the reset command.
Also the different maintenance counters are not affected but must be resetted manually at the UMC100-PAN.
The reset command can be activated via:
• UMC100-PAN

Resetting the password

The password can always be set or disabled using the UMC100 DTM (PBDTM) or using the UMC100-PAN.

Reading, setting and resetting maintenance counters

Preventive maintenance is the best way to ensure the long service life of any equipment.
The UMC provides several counters which help to better plan maintenance activities or to track down an existing problem.
• Number of motor starts can help to identify worn-out power contacts or to determine on contactor wear
• Number of protection trips
• Motor operation hours can help to assess the bearing status and its lubrication
The maintenance counters are available at the UMC100-PAN and in the PBDTM.

I/O-Module status codes

Three LEDs show the module status. The following table explains the status messages.
Status
Green LED
Yellow LED
On
On
Flashing
Off
Flashing
Off
On
Off
On
Flashing
Irrelevant
Explanation
Red LED
On
Self-test during start-up
On
Communication with UMC was interrupted. Relay outputs switched off.
Possible cause: Wiring between UMC and I/O module broken.
Possible corrective measure: Check wiring and check that the module was activated in the UMC
configuration.
Off
Waiting for communication with UMC. Module is ready.
Possible cause: Wiring between UMC and I/O module broken.
Possible corrective measure: Check wiring and check that the module was activated in the UMC
configuration.
Off
Cyclic data exchange with UMC. No diagnosis.
Off
Cyclic data exchange with UMC. Diagnosis exists.
Flashing
Hardware defect.
Possible corrective measure: Replace module.