Chapter 7
Settings and configuration
7:2.4.6 Outputs
To set parameters related to the programmable outputs, enter the Outputs group.
Start / Stop
Relay K4
Protections
Select the required function for output relay K4.
One of the following functions can be selected:
Warnings
Run
Run indication.
Faults
TOR Top of ramp indication.
Inputs
Event Indication of selected event(s) . The following events can be selected individually:
Outputs
• Motor overload protection
• Fault
Fieldbus
• High current protection
• SCR overload protection
Seq. Start
• Locked rotor protection
• Underload protection
• Phase imbalance protection
Press Store to save/activate the selected function.
Relay K5
Select the required function for output relay K5.
One of the following functions can be selected:
Run
Run indication.
TOR Top of ramp indication.
Event Indication of selected event(s), see relay K4.
Press Store to save/activate the selected function.
Relay K6
Select the required function for output relay K6.
One of the following functions can be selected:
Run
Run indication.
TOR Top of ramp indication.
Event Indication of selected event(s), see relay K4.
Press Store to save/activate the selected function.
SW Outp V7
Select the required function for the fieldbus communication output SW Outp V7.
One of the following functions can be selected:
Run
Run indication.
TOR Top of ramp indication.
Event Indication of selected event(s), see relay K4.
Press Store to save/activate the selected function.
Fieldbus
To set parameters related to the fieldbus communication, enter the Fieldbus group.
Start / Stop
Fieldbus control (Fieldb Ctrl)
Protections
Activate the fieldbus control by changing to Yes.
Press Store to save the selected function.
Warnings
Fieldbus type (Fieldb Type)
Faults
Select what fieldbus type is used.
Inputs
AS-Interface Used for AS-I protocol.
Other
Outputs
Press Store to save/activate the selected function.
Fieldbus
Fieldbus address (Fieldb Addr)
Set a unique address number between 1 and 1000 for fieldbus communication.
Seq. Start
Press Store to save the selected function.
!
The motor may start unexpectedly if there is a start signal present when doing any of the
actions listed below:
• Switching from one type of controol to another (fieldbus control/hardwire control)
• Re-programming the programmable inputs.
• Reset all Settings (programmable input set to Enable)
Used for protocols other than AS-I (i.e., DeviceNet, Profibus DP, Modbus).
Caution!
• Shunt fault
• Low current warning
• High current warning
• SCR overload warning
• Overload warning
• Phase reversal protection
• PTC protection