Advertisement

Application Setting
Select
Back
Figure 4: Application setting menu
Centrifugal Pump
Store Set
Figure 5: Centrifugal pump
Centrifugal Pump
Next
Figure 6: Centrifugal pump stored
Setting Ie
99.0A
Store
Figure 7: Setting Ie
Setting Ie
99.0A
Next
Figure 8: Setting Ie stored
OL Class
Store
Figure 9: OL Class
OL Class
Next
Figure 10: OL Class stored
Ext ByPass
Store
Figure 11: External Bypass
Ext ByPass
Next
Figure 12: External Bypass stored
Ready?
Yes
Tune Set
Figure 13: Ready / Tune Set
Low Voltage Products & Systems
ABB nc. • 888-385-1221 • www.abb-control.com
Chapter 2
Quickstart
2:2 Configuration
1. Enter the Application Setting by pressing the left selection key twice. Press Select using the
left selection key. See Figure 4.
2. Select the appropriate type of load by using the navigation keys. See Figure 5.
3. Press Store Set and Next to continue or Back to previous parameter using the selection
keys. See Figure 6.
4. Set Ie (motor FLA) using the navigation keys.
In Line connected = rated motor current
Back
Inside Delta connected = 58% (1/( 3)) of the rated motor current. For example, if the soft
starter is connected in line with a 100A motor, Ie = 100A. If the softstarter is connected inside
the delta of a 100A motor, Ie = 58A. See Figure 7.
5. Press Store and Next to continue or press Back to access the previous parameter. See Fig-
ure 8.
Back
6. Set the required overload class using the navigation keys. See Figure 9.
7. Press Store and Next to continue or press Back to access the previous parameter. See Fig-
ure 10.
8. If an external by-pass contactor is used set Ext ByPass to Yes using the navigation keys.
(PST30...300 only). See Figure 11.
9. Press Store and Next to continue or Back to previous parameter using the selection keys.
See Figure 12.
10. Select Yes if ready or Tune Set if ramp times, initial voltage, current limit etc. need to be
adjusted. See Figure 13.
Back
11. To change language, see Section 7:2.5.
2:3 Start of the motor
1. Switch on the main voltage.
10
2. Give a start command to the softstarter.
(To start the softstarter from the keypad, enter the LOCAL CONTROL menu, select Start/
Stop and press Start. The motor must be stopped before leaving this menu.)
10
Back
No
No
Back
2
2.3
1SXU 132 021 M0201