ABB PST30 Installation And Maintenance Manual page 60

Pst series; pstb series
Hide thumbs Also See for PST30:
Table of Contents

Advertisement

Top level
Settings
Figure 36: Reset all Settings menu
Top level
Settings
7
Figure 37: Reset all Settings menu
Operation Mode
Select
Figure 38: Display appearance in normal mode
Operation Mode
Select
Figure 39: Display appearance in demo mode
7.22
1SXU 132 021 M0201
Chapter 7
Settings and configuration
7:2.7.2 Reset All Settings
To reset all the changed parameters back to factory default settings, enter this menu.
Application setting
Confirmation of reset will be displayed as Done on the LCD. The supply voltage should
Basic settings
also be disconnected and reconnected.
The real time clock, the hour run meter, the number of starts and the presentation lan-
Functional settings
guage will not be affected by the reset.
Presentation settings
Service settings
All settings
Changed settings
The motor may start unexpectedly if there is a start signal present when doing any
Reset all settings
of the actions listed below.
Operation mode
• Switching from one type of control to another (fieldbus control / hardwire control)
• Re-programming the programmable inputs
• Reset all Settings (programmable input set to Enable)
7:2.7.3 Operation (test) mode
The Operation mode makes it possible to switch between two different modes in the
Application setting
softstarter: a demo mode and the regular operation mode. By entering the demo mode,
Basic settings
programmable inputs/outputs, start and stop circuits, by-pass contactor etc. can be
tested before the unit is put into operation. As long as the unit is in demo mode, the color
Functional settings
on the display is inverted (except on the external keypad).
Presentation settings
Service settings
All settings
Never enter the demo mode with the main voltage connected. The by-pass contactor will
Changed settings
close at TOR and may start the motor.
Reset all settings
Operation mode
Back
Back
!
Caution!
!
Caution!
Information!
The total run time of the motor and the total number of starts will be counted also
during demo mode. When exiting demo mode, these values will be reset to previous
values. Parameters changed and the Event Log will be kept when exiting demo mode.