Mitsubishi Electric MELSEC iQ-R Series Safety Manual page 129

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

For details on the safety FBs, refer to the following.
 MELSEC iQ-R Safety Function Block Reference
In this example, an enabling switch with no monitor signal for position 3 is used. Therefore, SA\SM400 (Always on) is
connected to the input signal, i_bS_EnableSwCh2, of M+SF_ENBLSW_R.
When using an enabling switch with monitor signal for position 3, connect the signal to i_bS_EnableSwCh2 to monitor the
status of position 3.
■Timing chart
Mode switched
Mode: Automatic (mode_auto)
Mode: Manual (mode_manu)
M+SF_MODESEL_R S_Mode1Sel
output (SA\M11)
M+SF_MODESEL_R S_Mode0Sel
output (SA\M10)
Reset switch (reset_in)
Start switch (start_in)
M+SF_EDM_R reset input (SA\M3)
Interlock status (SA\SD1232.0)
Interlock release request
(SA\SD1240.0)
Safety refresh communication
status (SA\SD1008.0)
Safety switch (SA\X0)
Enabling switch (SA\X8)
M+SF_ENBLSW_R safety output
(SA\M5)
Contactor output (SA\Y0)
Contactor output check (SA\X2)
M+SF_EDM_R Error output
(SA\M2)
In manual mode, the reset switch and start
switch cannot be used.
Guard opened
Enabling
Enabling
Enabling
Enabling
switch
switch
switch
switch
turned on
turned on
turned off
turned off
In manual mode, the M+SF_GMON_R is disabled
and the operation using the enabling switch is
possible even though the guard is open.
Error occurred in
Error occurred in
a safety remote
a safety remote
I/O module
I/O module
A safety remote I/O module detects
a double input discrepancy.
When an error occurs in a safety remote I/O module, inputs
and outputs of the safety remote I/O module are turned off.
Also, the M_SF_MODESEL_R, M_SF_ENBLSW_R,
M+SF_GMON_R, and M+SF_EDM_R are disabled.
5 SAFETY APPLICATION CONFIGURATION EXAMPLES
5.1 System Configured by a Safety CPU
5
Contact welding
Contact welding
detected in the
detected in the
contactor 1
contactor 1
127