Relationship Between Devices In The Safety Cpu And Remote Inputs/Outputs - Mitsubishi Electric MELSEC iQ-R Series Safety Manual

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Relationship between devices in the Safety CPU and remote
inputs/outputs
The following shows the relationship between the Safety CPU device, the inputs/outputs of safety remote I/O module, and the
standard remote I/O module according to the settings on Page 58 Parameter settings of CC-Link IE Field Network. Use
devices in shaded areas in the program.
For standard programs
Station
X1F-X110
X10F-100
No.2
Station
W0113-W0100
No.2
Station
W0213-W0200
No.2
The system uses 16 points each of the RWr/RWw to communicate with the safety remote I/O module. Set 16 points each of
the RWr/RWw according to Page 58 Parameter settings of CC-Link IE Field Network. Do not read/write data from/to the RWr/
RWw to be used by the system. Writing data may cause malfunction of the safety programmable controller.
For details, refer to the following.
 CC-Link IE Field Network Remote I/O Module (With Safety Functions) User's Manual
5 SAFETY APPLICATION CONFIGURATION EXAMPLES
72
5.1 System Configured by a Safety CPU
Safety CPU
CC-Link IE Field Network
master/local module
For safety programs
Station
SA\X1F - SA\X0
No.1
SA\X3F - SA\X20
SA\X5F - SA\X40
SA\X7F - SA\X60
SA\Y1F -
SA\Y7 -
Station
SA\Y8
SA\Y0
No.1
SA\Y3F - SA\Y20
SA\Y5F - SA\Y40
SA\Y7F - SA\Y60
Main module
NZ2GFSS2-32D
RX
RX005F-RX0050
RWr
0023-0010
RWw
0023-0010
Safety remote I/O module
(station No.1)
CCIEF remote (1): SR_IO1
Extension module
NZ2EXSS2-8TE
X1F-X0
Y7-Y0
Standard remote I/O module
(station No.2)
CCIEF remote (2): R_IO2
Main module
NZ2GF2B1-16D
XF-X0
RWr
0013-0000
RWw
0013-0000