■Wiring diagram and parameter setting
Wire the emergency stop switches and safety relays to safety remote I/O module of safety programmable controllers (1) to (3)
as follows. For details on the terminal block, refer to the following.
 CC-Link IE Field Network Remote I/O Module (With Safety Functions) User's Manual
Emergency
1
stop switch*
[3]
Safety relay
[1]
[4]
Safety relay
[2]
Network number 2, 3, or 4 is placed to A.
Above [1] to [4] are connected to the one with same numbers.
*1 Connect an emergency stop switch having two normally closed contacts with direct opening mechanism between input terminal and test
pulse terminal.
*2 Connect normally closed contact of the safety relay between the input terminal and test pulse terminal.
5 SAFETY APPLICATION CONFIGURATION EXAMPLES
176
5.2 System to Which Multiple Safety CPUs are Connected
CCIEF remote (A-1)
NZ2GFSS2-32D
Network No.A (A = 2, 3, 4)
Station No.1
24VDC
A1
+24V
A2
+24V
A3
24G
A4
24G
A5
FG
24VDC
19
IO24V
20
IO24G
1
X0
2
X1
[1]
3
X2
[2]
4
X3
5
X4
21
T0
22
T1
23
T0
[3]
2
*
24
T1
[4]
CCIEF remote (A-1)
NZ2EXSS2-8TE
Network No.A (A = 2, 3, 4)
Station No.1
24VDC
19
IO24V
20
IO24G
1
Y0
2
COM-
3
Y1
4
COM-
Terminal block for power supply and FG (input)
A1
+24V
A2
+24V
A3
24G
A4
24G
A5
FG
Spring clamp terminal block (input)
Spring clamp terminal block (output)