Downloading And Starting Plc Application - ABB COM600 series 5.1 User Manual

Logic processor
Table of Contents

Advertisement

3.3.5.
22
COM600 series 5.1
Logic Processor User's Manual
Figure 3.3.4-3 Select Device Active Path to COM600
6. Once the active path is set, the Device Communication Settings page should show
up as below. Further downloads can be accomplished by login to device.
Figure 3.3.4-4 Device Communication Settings after setting active path

Downloading and starting PLC application

After setting the device active path between Logic Editor and Logic Processor, PLC
Application can be built and downloaded to Logic Processor.
To download and start PLC Application:
1. Select Build from the menu bar in Logic Editor, and click Build to build and compile
PLC Application in a project. All objects belonging to this application are syntactic-
ally checked. Any potential error messages or warnings are displayed in the message
view.
1MRS756738
Select_Device_Active_Path.png
Device_Communication_Settings_Active_Path.png