Configuration; Overview Of Configuring Logic Processor; Building Communication Structure Objects - ABB COM600 series 5.1 User Manual

Logic processor
Table of Contents

Advertisement

1MRS756738
3.
3.1.
3.2.
COM600 series 5.1
Logic Processor User's Manual

Configuration

Overview of configuring Logic Processor

The prerequisite is to have knowledge about logic programming and IEC 61131-3
standard.
Also, CoDeSys programming environment must be installed from the SAB600 DVD to
be able to use the Logic Editor in SAB600. The version of the programming environment
is dependent on the used COM600 version. The installed versions can be selected during
the setup. For information about CoDeSys programming environment installation, see
COM600 User's Manual.
Before starting to configure the Logic Processor, it is necessary that the process commu-
nication has been configured.
The Logic Processor configuration in COM600 can be divided into the following tasks:
1. Building Communication Structure objects for the Logic Processor.
2. Creating the logic in the CoDeSys programming environment.
3. Building a cross-reference between process data and logic variables data by using
the Cross-References tool.
4. Creating virtual data objects in the Logic Processor OPC server and connecting the
data objects to logic variables with the object properties.

Building communication structure objects

To build the communication structure:
1. Add the Logic Processor OPC Server object in the Communication structure by
selecting the Gateway object.
2. Right-click the Gateway object and select New > Logic Processor OPC Server.
3. Right-click the Logic Processor OPC Server object and add Logic Processor Sub-
network.
4. Right-click the Logic Processor Subnetwork object and add Logic Processor IED.