Building And Activating The Application - ABB COM600 series 5.1 User Manual

Logic processor
Table of Contents

Advertisement

1MRS756738
4.8.
4.9.
COM600 series 5.1
Logic Processor User's Manual
Figure 4.7-1 Device Communication Settings after setting active path

Building and activating the application

1. Select Build > Build to compile the project.
All objects belonging to the application is syntactically checked. Any potential error
messages or warnings are displayed within the message view.
2. If the project is built successfully without error, select Online > Login to connect
to the currently active application to the target device PLC and thus changes into
the online mode.
If there is no application running on target device before Login, the current active
application is downloaded to the device.
3. Select Debug > Start to start the program on the PLC.
The program starts running.
4. Select Online > Logout to log out from the device and File > Exit to close the logic
processor configuration tool.
Making cross-references
After logging out from the device, close the Logic Editor and launch the Cross References
tool in SAB to build further cross-references between the COM600 communication
structure and Logic Processor variables.
To make cross-references:
1. In SAB600, right click Logic Processor IED and select Cross References.
2. The Cross References tool reads all the symbols defined in Logic Processor. The
variable selected from the Logic Editor Symbol Configuration is show in the OPC
Item column.
Device_Communication_Settings_Active_Path.png
37