Figure 4.5-1 Adding POU to MainTask

Add Symbol Configuration

To configure symbols from POU:
1. Right-click Application in the Device Tree. Select Add Object > Symbol Config-
uration.
2. A Symbol Configuration object is added to Application and Symbol Configuration
Editor opens.
3. To get the currently available item pool, click Build. Resolve any errors.
4. Add variables from POU to Application Symbol list by simply clicking the
checkbox next to each of the variables and assigning appropriate access rights. Select
variable,
a.
br2Failure, and set access right to "read"
b.
br1SelectTrip, and set access right to "write"
c.
br1Trip, and set access right to "write"
d. br2SelectTrip, and set access right to "write"
e.
br2Trip, and set access right to "write"
f.
br3SelectTrip, and set access right to "write"
g. br3Trip, and set access right to "write"
h. reset, and set access right to "read"