Adding Logic Processor Ied; Creating Logic Configuration - ABB COM600 series 5.1 User Manual

Logic processor
Table of Contents

Advertisement

4.3.
4.4.
30
COM600 series 5.1
Logic Processor User's Manual
a.
Add one DPC data object (Pos) to read and control the switch.
b.
Add one SPS data object (BreakFailure) to read break failure signal.
6. In breaker 3 IED, add a logic node Brk3CSWI1.
a.
Add one DPC data object (Pos) to read and control the switch.

Adding Logic Processor IED

To add a Logic Processor IED:
1. In SAB600, under Gateway, add Logic Processor OPC Server.
2. Under Logic Processor OPC Server, add Logic Processor Subnetwork.
3. Add Logic Processor IED.
Figure 4.3-1 Adding Logic Processor IED

Creating logic configuration

To build logic configuration:
1. Right-click on Logic Processor IED in SAB600 and select Logic Editor to launch
the CoDeSys programming environment.
2. The logic editor starts with a new project.
3. Select Add object from the Project menu.
4. Select POU on the left side of the Add Object dialog.
5. Enter a name "PLC_BreakerFailureProtection" for the POU and select the Program
radio button in the Type section.
6. Select Function Block Diagram (FBD) for the implementation language.
1MRS756738
Add_Logic_Processor_IED.bmp