26
500...600 volt, fuse recommendations
ACH580-01-
02A7-6
03A9-6
06A1-6
09A0-6
011A-6
017A-6
022A-6
027A-6
032A-6
041A-6
052A-6
062A-6
077A-6
099A-6
125A-6
144A-6
180A-6
242A-6
271A-6
1) ABB does not require Bussmann brand fuses. Fuses which meet the appropriate UL class type,
current rating, and are rated at 600V, 200 kA may be used.
ACH580-01 Installation
ACH580 Installation, Operation and Maintenance Manual
Input
Maximum
current
Voltage rating
current
A
A
3-phase U
2.7
15
3.9
15
6.1
15
9
15
11
15
17
30
22
40
27
40
32
40
41
100
52
100
62
100
77
100
99
150
125
200
144
250
180
300
242
400
271
400
UL
Bussmannn type
V
= 575 V
N
600
KTK-R-15 or JJS-15
600
KTK-R-15 or JJS-15
600
KTK-R-15 or JJS-15
600
KTK-R-15 or JJS-15
600
KTK-R-15 or JJS-15
600
KTK-R-30 or JJS-30
600
JJS-40
600
JJS-40
600
JJS-40
600
JJS-100
600
JJS-100
600
JJS-100
600
JJS-100
600
JJS-150
600
JJS-200
600
JJS-250
600
JJS-300
600
JJS-400
600
JJS-400
1
UL class
Class CC or T
Class CC or T
Class CC or T
Class CC or T
Class CC or T
Class CC or T
Class T
Class T
Class T
Class T
Class T
Class T
Class T
Class T
Class T
Class T
Class T
Class T
Class T

Hide quick links: