Fuses; 208…240 Volt, Fuse Requirements - ABB ACH580 Series Installation, Operation And Maintenance Manual

Hide thumbs Also See for ACH580 Series:
Table of Contents

Advertisement

24

Fuses

Note: The UL listed fuses in the table are the required branch circuit protection.
Fuses are to be provided as part of the installation.
• Fuses are not included in the purchased drive and must be provided by others.
• Fuses with higher current rating than specified must not be used.
• Fuses with lower current rating than specified may be used if they are of the same
class and voltage rating. It is the user's responsibility to verify that lower current
rated fuses are compliant with local regulations and appropriate for the
application.
• Drive fuses must be used to maintain the drive UL listing. Additional protection
can be used. Refer to local codes and regulations.
208...240 volt, fuse requirements
ACH580-01-
04A6-2
06A6-2
07A5-2
10A6-2
017A-2
024A-2
031A-2
046A-2
059A-2
075A-2
088A-2
114A-2
144A-2
169A-2
211A-2
273A-2
1) ABB does not require Bussmann brand fuses. Fuses which meet the appropriate UL class type,
current rating, and are rated at 600V, 200 kA may be used.
ACH580-01 Installation
ACH580 Installation, Operation and Maintenance Manual
Input
Maximum
current
Voltage rating
current
A
A
3-phase U
4.6
15
6.6
15
7.5
15
10.6
15
16.7
30
24.2
40
30.8
40
46.2
80
59.4
80
74.8
100
88
150
114
150
143
200
169
250
211
300
273
400
UL
Bussmannn type
V
= 208 V
N
600
KTK-R-15 or JJS-15
600
KTK-R-15 or JJS-15
600
KTK-R-15 or JJS-15
600
KTK-R-15 or JJS-15
600
KTK-R-30 or JJS-30
600
JJS-40
600
JJS-40
600
JJS-80
600
JJS-80
600
JJS-100
600
JJS-150
600
JJS-150
600
JJS-200
600
JJS-250
600
JJS-300
600
JJS-400
1
UL class
CC or T
CC or T
CC or T
CC or T
CC or T
T
T
T
T
T
T
T
T
T
T
T

Hide quick links:

Advertisement

Table of Contents
loading