18 Repeater (SAFEDLINK) FN2002-A1
18.1
Building Technologies
Fire Safety
Description
The repeater (SAFEDLINK) FN2002-A1 is used to extend the range with the FCnet
system bus. The repeater is built on the basis of the network module (SAFEDLINK)
and allows the FCnet line between two stations to be extended by 1000 m.
The repeater (SAFEDLINK) has the following features:
Connections for remote supply and supply transmission to a second repeater
Cable shields individually placed onto the ground by means of jumpers (HF
low-impedance / NF high-impedance)
Data rate of the FCnet can be switched via a jumper
Electrical isolation of the SAFEDLINK system bus
Electrical connection between the power supply and the station
Earth fault monitoring
EMC protection on system bus and power supply
Repeater (SAFEDLINK) FN2002-A1
Description
18
111
008837_q_en_--
14.05.2012