Fire detection system
Table of Contents

Advertisement

Configurable inputs/outputs
1...12
Connection terminals
Mechanical data
Building Technologies
Fire Safety
Designation
Individually configurable as
Configured as input
Design
Threshold values
Configured as output:
Design
Output voltage
Output current per output
Output current of all outputs (total)
Inputs, outputs and FDnet
Design
Admissible cable cross-section
Supply
Design
Admissible cable cross-section
Dimensions (L x W x H)
Weight
Some voltage ranges of certified horns are limited to 28 V. This maximum voltage
1
can only be guaranteed if the control panel temperature is >5 °C.
Periphery board (4 loops) FCI2004-A1
Technical data
'I/O1' ... 'I/O12'
Input
Output
Digital
Not monitored
> Vsys/2 = off
< Vsys/4 = on
Open drain
Inherently short-circuit-proof
Excess temperature protection
DC 21...28.6 V
Max. 300 mA
1.5 A
Screw terminals
0.2...1.5 mm²
Screw terminals
0.5...2.5 mm²
210 x 225 x 40 mm
350 g