X2 Monitoring Signals; Indicators - Siemens 13-xx-ST-SBT Series Product Data

Fire detection system
Table of Contents

Advertisement

3
Power supply (70 W) FP2001-A1

Indicators

3.3.2
3.4 Indicators
LED
Color
Function
MAINS
Yellow
Monitoring of
voltage surveillance
(H202)
BATT
Yellow
Monitoring of battery On
(H201)
CONV
Green
Monitoring of power
supply
(H200)
24
Building Technologies
Fire Safety

X2 monitoring signals

Pin
Designation
8
Battery
7
Convert
6
Main
5
Common GND
4
Usys +
3
Usys –
2
Akku +
1
Akku –
Admissible cable cross-section: 0.2...2.5 mm²
Battery
Convert
Main
Common GND
Usys +
+
Usys -
-
+
Akku +
F103
-
Akku -
F102
1 Cable tree to periphery board or fire terminal board
See also
X1 supply [
X1 supply [
X1 supply [
Condition
On
Off
Off
On
Off
Description
Detection line (#BATT): Battery fault
Detection line (#CONV): Power supply fault
Detection line (#MAINS): Mains fault
Ground (COMMON)
System supply (VSYS+)
System supply (VSYS-)
Battery supply (+)
Battery supply (–)
X2
#BATT
8
#CONV
7
6
#MAINS
COMMON
5
4
VSYS+
3
VSYS-
2
1
46]
70]
57]
Meaning
No mains voltage, fault in the primary supply
Normal condition
Battery fault
Normal condition
Normal condition
Power supply fault
1
008837_q_en_--