Sounder Module Fca2005-A1; Description - Siemens 13-xx-ST-SBT Series Product Data

Fire detection system
Table of Contents

Advertisement

31

Sounder module FCA2005-A1

Description

31 Sounder module FCA2005-A1
31.1
180
Building Technologies
Fire Safety
Description
The sounder module FCA2005-A1 makes it possible to assign a monitored horn
output of the periphery board FCI2002-A1 or FCI2004-A1 to up to four horn
outputs. Each of these four lines has the same features as the sounder output of
the periphery board and may control and monitor alarm devices. Supply is ensured
via the supply output of the periphery board.
The sounder module may only be fitted and operated in the fire control panel.
It can be fitted as follows:
Engaged on a 35 mm DIN rail
Screwed onto an even surface (mounting plate)
Clamped into a FDCH291 / FDCH292 housing. This housing can also be
screwed onto an even surface (mounting plate).
008837_q_en_--