Adjustment Elements; Technical Data - Siemens 13-xx-ST-SBT Series Product Data

Fire detection system
Table of Contents

Advertisement

6
Fire terminal board FTI2001-A1

Adjustment elements

6.5 Adjustment elements
Switch
Function
S1-1
Supply input 1 'VSYS1'
S1-2
Supply input 2 'VSYS2'

6.6 Technical data

Supply
(connector X1)
Input 3rd supply source
(connector X1)
Power supply input 1
(connector X7)
Power supply input 2
(connector X6)
Supply output
(connector X5)
Connection terminals
Mechanical data
50
Building Technologies
Fire Safety
Position Meaning
ON
OFF
ON
OFF
Designation
Operating voltage
Operating current
Designation
Voltage
Current
Designation
Voltage
Current
Designation
Voltage
Current
Designation
Voltage
Current
Inputs and outputs:
Design
Admissible cable cross-section
Dimensions (L x W x H)
Weight
Input is not used (default setting)
Input is used (monitored)
Input is not used (default setting)
Input is used (monitored)
'VSYS+'; 'VSYS-'
DC 21...28.6 V (= Usys)
Max. 2.5 A
'3SRC+'; '3SRC-'
DC 7...30 V
Max. 40 mA
'VSYS +1', 'VSYS -1'
DC 21...28.6 V (= Usys)
Max. 2 A
'VSYS +2', 'VSYS -2'
DC 21...28.6 V (= Usys)
Max. 2 A
'VSYS 1', 'VSYS 2'; 'GND 1', 'GND 2'
DC 21...28.6 V
Max. 1 A per output
Spring clips
0.2...2.5 mm²
210 x 150 x 40 mm
130 g
008837_q_en_--
14.05.2012