Indicators; Technical Data - Siemens 13-xx-ST-SBT Series Product Data

Fire detection system
Table of Contents

Advertisement

18
Repeater (SAFEDLINK) FN2002-A1

Indicators

18.4
LED
Color
Function
H1
Green
Condition of the repeater
(SAFEDLINK)
H2
Yellow
Condition of the line 2
(A2, B2)
H3
Yellow
Condition of the line 1
(A1, B1)
H4
Red
Ground fault
18.5
Supply input
System bus
Connections
Mechanical data
Standards
114
Building Technologies
Fire Safety
Indicators
Condition
Flashes
Off
On
Off
On
Off
On
Off

Technical data

Voltage
Operating current
Voltage
Current
Impedance
Protocol
Data rate in operation mode:
Speed
Distance
Distance between repeater and network module
Electrical isolation between the FCnet and the
station
Monitored for:
System bus:
Design
Operating unit
Dimensions (W x H x D)
Weight
VdS
The supply voltage may significantly decrease along the supply line from the
1
station to the repeater. To ensure the reliable operation of the repeater, the
terminal voltage must be at min. 9 V.
Meaning
Normal condition
Repeater (SAFEDLINK) is defective
Fault on connection line 2;
Repeater (SAFEDLINK) is OK
Normal condition
Fault on connection line 1;
Repeater (SAFEDLINK) is OK
Normal condition
Ground fault on connection line 2;
Repeater (SAFEDLINK) is OK
Normal condition
DC 9...30 V
Max. 45 mA
DC 5 V
Max. 100 mA
120
SAFEDLINK (UDP/IP)
312 kbit/s
96 kbit/s
Max. 1000 m
1 kV
Short-circuit
Open line
Ground fault
Communication error
Screw terminals type Phoenix
MC1,5/x-ST-3,81
0.8 ... 1.5 mm
(0.8 mm
Plug-type connection
90 x 25 x 132 mm
105 g
G211003
1
2
recommended)
2
008837_q_en_--
14.05.2012