30.5
Building Technologies
Fire Safety
LED
Color
Function
OUT1
Yellow Status monitored
output 1
OUT2,3 In accordance with OUT1, although at monitored output 2 and 3
FA_R
Yellow Relay fault output
AL_R
Yellow Relay alarm output
MSP
Yellow Status
Line driver
Adjustment elements
Button
Meaning
CALIB, S501
Calibration
I/O card (RT) FCI2007-A1
Adjustment elements
Condition
Meaning
Off
Normal operation
Slow
Fault:
Connection interrupted or
short-circuited
(Priority 2)
Fast
Fault:
Overload fuse active
(Priority 1)
Pulsating
- Calibration invalid
- Calibration running
(maximum 25 seconds)
(Priority 3)
On
Output activated
(Priority 4)
Off
Output is not activated
On
Output is activated
Off
Output is not activated
On
Output is activated
Off
Normal operation
Slow
Line driver in degraded mode
(Priority 2)
Fast
General fault or fault at supply
input 27V2
(Priority 1)
Pulsating
On
Function
Starts the calibration of the monitored outputs
30
---
---
177
008837_q_en_--