X1 Supply Input And Sounder Input From The Periphery Board; Indicators; Technical Data - Siemens 13-xx-ST-SBT Series Product Data

Fire detection system
Table of Contents

Advertisement

31
Sounder module FCA2005-A1

Indicators

31.3.4
X1 sounder module
Pin
Designation
1
+Vsys
2
Ground
3
Sound In +
4
Sound In -
31.4
LED
Color
Function
H1
Green
Supply
H2
Yellow
Sounder 2 fault
H3
Yellow
Sounder 1 fault
H4
Yellow
Sounder 3 fault
H5
Yellow
Sounder 4 fault
31.5
Supply input
184
Building Technologies
Fire Safety
X1 supply input and sounder input from the periphery
board
Description
Supply input from the
periphery board (+)
Supply input from the
periphery board (-)
Sounder input from the
periphery board (+)
Sounder input from the
periphery board (-)
Admissible cable cross-section: 0.08...1.5 mm²
X1
Vsys
1
Ground
2
+
Sound In+
3
-
Sound In-
4
Indicators
Condition
Off
On
Off
On
Off
On
Off
On
Off
On

Technical data

Designation
Operating voltage
Quiescent current
Operating current
Periphery board
2 loops
Pin
Designation
X8-5
VSYS_01 (+)
X8-6
GND_01 (-)
X6-1
SOUND1+
X6-2
SOUND1-
Meaning
No supply (fuse may be defective)
Normal condition
Normal condition (default)
Sounder 2 fault (open line, short-circuit)
Normal condition (default)
Sounder 1 fault (open line, short-circuit)
Normal condition (default)
Sounder 3 fault (open line, short-circuit)
Normal condition (default)
Sounder 4 fault (open line, short-circuit)
'Vsys', 'Ground'
DC 21...28.6 V
20 mA, typical
Max. 2 A, protected with 2AT
Periphery board
4 loops
Pin
Designation
X8-7
VSYS_01 (+)
X8-8
GND_01 (-)
X5-1
SOUND1+
X5-2
SOUND1-
2
008837_q_en_--
14.05.2012