5.5.2

Manipulated variable filter

You activate the manipulated variable filter using parameter p1800.0 = 1. Entering a nominal
natural frequency = 0 or deactivating with p1800.0 = 0 deactivates the filter.
Note
The filter machine data must be assigned before the filter type is configured.
The type of manipulated variable filter is entered in parameter p1801.
Table 5- 4
Bit 0
The main filter data are defined using p1802, p1803 and p1804 up to p1805.
Enter the natural frequency for the manipulated variable filter (PT2 low-pass filter).
● Enter the damping for the manipulated variable filter (PT2 low-pass filter, p1803).
● Enter the numerator natural frequency for the manipulated variable filter (general 2nd
order filter, p1804)
● Enter the numerator damping for the manipulated variable filter (general 2nd order filter,
p1805)
Overview of important parameters (see SINAMICS S120/S150 List Manual)
• p1800[0...n]
• p1801[0...n]
• p1802[0...n]
• p1803[0...n]
• p1804[0...n]
• p1805[0...n]
Hydraulic Drive
System Manual, 04/2015, 6SL3097-4BA00-0BP1
Type of manipulated variable filter
0
PT2 low-pass filter (see p1802/p1803)
1
General 2nd order filter (see p1804/p1805)
Manipulated variable filter activation
Manipulated variable filter type
Manipulated variable filter denominator natural frequency
Manipulated variable filter denominator damping
Manipulated variable filter numerator natural frequency
Manipulated variable filter numerator damping
Drive functions
5.5 Control voltage output
177