3.2.3.3
Switch-off signal path
You can test the switch-off signal paths in the "Switch-off signal path" setting area. Follow the
instructions in the detailed display.
Figure 3-4
You can make the following settings here, for example:
● Enter conditions to initiate the test
● Select acquired alarms that should appear in the report
● Confirm a test result
3.2.3.4
Function relations
User-specific test cases for safety-related functions can be saved in test type "Function
relations". After the test case has started, the user executes the steps required at the system
itself. He observes the response/behavior, and documents the test result that has been
monitored.
Example of a function to be tested
When the machining area door is opened, safety function "Safe Operating Stop" (SOS) must
be selected for all axes of mode group 1.
SINUMERIK Operate acceptance test
Function Manual, 08/2018, A5E39460574B AC
3.2 SINUMERIK 828D/840D sl - drive-based Safety functions
Test type/setting range switch-off signal path
Acceptance test wizard of SINUMERIK Operate
29