Warning
Danger of electric shock
An electric shock can result from touching live parts in the installation environment.
Electric shock can cause death.
Pay attention to the installation regulations:
• Route the bus line with the sheathing intact until it is close to the bus connection ter-
minal.
• Firmly press the bus line into the bus connection terminal as far as possible.
• Install bus line leads without sheathing (SELV) reliably disconnected from all non-
safety low-voltage cables (SELV/PELV).
• Maintain the specified clearance.
• Attach the cover cap supplied.
• For more information, see also the VDE regulations governing SELV (DIN VDE 0100-
410/"Safe separation", KNX installation regulation).
Manually resetting the device to the factory settings
Requirement: the device must be switched off without voltage.
1.
Press the programming button (see figure 19, item 1) and keep it pressed while you attach the
power connection terminal.
2.
Do not release the programming button until the following LEDs are all flashing slowly at the same
time:
• Programming LED (see figure 15, item 1)
• APP LED (see figure 15, item 2)
• COM LED (see figure 15, item 3)
Usual duration: approx. 30 seconds.
3.
Release the programming button briefly.
4.
Press the programming button again and keep it pressed until following LEDs are all flashing rap-
idly at the same time:
• Programming LED (see figure 15, item 1)
• APP LED (see figure 15, item 2)
• COM LED (see figure 15, item 3)
5.
Release the programming button.
The factory settings are being reset. You do not have to restart the device.
ISE SMART CONNECT KNX Panasonic
© 2019 ise Individuelle Software und Elektronik GmbH
Commissioning and configuration
1-000C-000
S. 34 / 69